Fire protection foam Kombi
Fire protection foam Kombi
FPFM-BS22K-COMBO
Art.-no. 0893303200
EAN 4053479198842
Register now and access more than 125,000 products
- Easy, quick installation
- No coating of cable or partition surface
- With the fire protection blocks, larger spaces in the partition can be closed quickly and cost-effectively
- Flexible foam, easy to add at a later stage
- Can be painted over
- Dust-free application
- PE and PVC pipes with diameter up to 50 mm without fire protection sleeve can be routed through
Wall and ceiling duct, fire-resistant Z-19.53-2337
Weatherboard materials made of cardboard or plastic can remain on the partition.
Clean opening.
Apply foam without interrupting the pump.
Cut off protruding material.
Affix ID plate.
Wall and ceiling duct, fire-resistant Z-19.53-2337
For detailed information on the partition, please refer to the general type approval Z-19.53-2337.
For use in system [D4]
Fire protection foam combination [D4]
For wall and ceiling ducts with fire resistance class fire-resistant for cable support systems, electrical installation pipes and flammable and non-flammable pipes.
Contents | 380 ml |
Container | Cartridge |
Colour | Red brown |
Fire resistance rating | Fire resistant |
Yield (volume) approx. | 2.1 l |
Can be cut after | 90 s |
Min. processing temperature | 20 °C |
Max. processing temperature | 25 °C |
Min. ambient processing temperature | 25 °C |
Conditions to maintain shelf life from production | dry storage area, 5°C to 30°C |
Shelf life from production | 12 Month |
| Range of applications | |
| Fire resistance classes EN 13501-2:2010 | EI 30//60/90/120 |
| In ceilings and walls made from | aerated concrete, concrete, reinforced concrete, masonry and light dividers with wooden or metal substructures according to EN 13501-2:2009 A1: > EI 90/REI 90 |
| For cables and pipes | Cables, telecommunication cables, fibre-optic cables, copper, steel, stainless steel and cast pipes, plastic pipes, electrical installation pipes |
| Maximum partition assignment | 60% |
| Permissible installation locations of the partitioning system | Combination partitioning (cables and pipes) | Cable partitioning | Components | Minimum thickness | Classification of the component | Fire resistance* | Minimum partition thickness* | Maximum partition dimensions | Fire resistance* | Minimum partition thickness* | Maximum partition dimensions |
| Solid wall: Aerated concrete, concrete, reinforced concrete, masonry | 100 mm | EN 13501-2 | EI 60 | 144 mm | W x H 450 x 500 (mm) | EI 60 | 100 mm/ 144 mm | 270 x 270 [mm] ∅ 300 mm |
| EI 90 | 144 mm/ 200 mm | |||||||
| EI 90 | 200 mm | EI 120 | 200 mm/ 250 mm | |||||
| Light divider: Wood or steel stand construction with panelling on both sides | 100 mm | EN 13501-2 | EI 60 | 144 mm | W x H 450 x 500 (mm) | EI 60 | 100 mm/ 144 mm | 270 x 270 [mm] ∅ 300 mm |
| EI 90 | 144 mm/ 200 mm | |||||||
| EI 90 | 200 mm | EI 120 | 200 mm/ 250 mm | |||||
| Solid ceiling: Aerated concrete, concrete, reinforced concrete | 150 mm | EN 13501-2 | EI 60 | 144 mm | W x H 450 x 500 (mm) | EI 60 | 100 mm/ 144 mm | 270 x 270 [mm] ∅ 300 mm |
| EI 90 | 144 mm/ 200 mm | |||||||
| EI 90 | 200 mm | EI 120 | 200 mm/ 250 mm | |||||
| * The required partition thickness depending on the fire resistance class and the installation performed can be found in the fire resistance classification tables. | ||||||||